Boiler Demand
To generate a Boiler Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Boil Dem and the Com Dem terminals (30 and 31).
Caution: The same power supply must be used to power the Boiler Demand, DHW
Demand and the Setpoint Demand circuits since they share the Com Dem terminal.
DHW Demand
To generate a DHW Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the DHW Dem and Com Dem terminals (29 and 31).
Caution: The same power supply must be used to power the Boiler Demand, DHW
Demand and the Setpoint Demand circuits since they share the Com Dem terminal.
Setpoint Demand
To generate a Setpoint Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Setp Dem and Com Dem terminals (28 and 31).
Caution: The same power supply must be used to power the Boiler Demand, DHW
Demand and the Setpoint Demand circuits since they share the Com Dem terminal.
Mix 1 Demand
To generate a Mix 1 Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Mix 1 Dem and the Com Dem terminals (25 and 26).
Caution: The same power supply must be used to power the Mix 1 Demand and the
Mix 2 Demand circuits since they both share the Com Dem terminal.
Mix 2 Demand
To generate a Mix 2 Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Mix 2 Dem and the Com Dem terminals (27 and 26).
Caution: The same power supply must be used to power the Mix 1 Demand and the
Mix 2 Demand circuits since they both share the Com Dem terminal.
Output Connections
Primary Pump Contact (Prim P1)
The Prim P1 output terminal (16) is a powered output. When the relay in the
control closes, 115 V (ac) is provided to the Prim P1 terminal (16) from the Power L
terminal (14). To operate the primary pump, connect one side of the primary pump
circuit to terminal 16 and the second side of the pump circuit to the neutral (Power N)
side of the 115 V (ac) power supply.
30
31
Boil
Dem
Com
Dem
24 to 230 V (ac)
29
DHW
Dem
30
Boil
Dem
31
Com
Dem
24 to 230 V (ac)
Aquastat
29
DHW
Dem
30
Boil
Dem
31
Com
Dem
28
Setp
Dem
24 to 230 V (ac)
25
26
Mix1
Dem
Com
Dem
24 to 230 V (ac)
26
27
Com
Dem
Mix2
Dem
24 to 230 V (ac)
14
L
15
16
Prim
P1
Power
N
N
L
115 V (ac)