11 of 32 © 2007 D 162 - 08/07
Mode Item Field Range Access Description
6
OFF, 40°F (4.5°C)
to Pool Maximum
Default = 78°F
(25.5°C)
LTD
USEr
InST
ADV
SET POOL OCCUPIED
SECTION F
Select the pool temperature during the occupied
period.
Note: In the Limited Access Level, the temperature
can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.
1
4
50 to 239°F
(10.0 to 115.0°C)
Default = 200°F
(93.5°C)
ADV
SETPOINT MAXIMUM SECTION A, D
Select the maximum setpoint temperature range
adjustment.
Note:
This item is only available when the mode
of operation is set to Heat.
2
50 to 104°F
(10.0 to 40.0°C)
Default = 104°F
(40.0°C)
ADV
HOT TUB MAXIMUM SECTION B
Select the maximum hot tub temperature range
adjustment.
3
50 to 200°F
(10 to 93.5°C)
Default = 140°F
(60.0°C)
ADV
DHW MAXIMUM SECTION C
Select the maximum indirect domestic hot water
tank temperature range adjustment.
5
50 to 110°F
(10.0 to 43.5°C)
Default = 85°F
(29.5°C)
ADV
FLOOR MAXIMUM SECTION E
Select the maximum floor temperature range
adjustment.
6
50 to 120°F
(10 to 49.0°C)
Default = 90°F
(32.0°C)
ADV
POOL MAXIMUM SECTION F
Select the maximum pool temperature range
adjustment.
4
5
6
CTRL, SYNC, 5 to
30 minutes
Default = CTRL
InST
ADV
CYCLE LENGTH
SECTION G
Select the heating or cooling cycle length in
minutes for PWM applications.
1
2
3
4
1 to 40°F
(0.5 to 22.0°C)
Default = 1F
(5.5°C)
InST
ADV
DIFFERENTIAL
Select the differential to cycle on and off around
the setpoint temperature.
ADJUST Menu (3 of 6)