Snow Detector & Melting Control 667
D 667
03/09
The Snow Detector & Melting Control 667 is a microprocessor-based control which operates a snow melting system. The control can
operate automatically when a Snow / Ice Sensor 090 is installed or the user can manually enable and / or disable the system. The
667 controls a variable speed injection pump to provide both boiler and slab protection. When the control is not in the Melting mode,
the system can either be shut down or it can be maintained at an idle temperature for faster response and improved safety. The 667
control includes a large Liquid Crystal Display (LCD) in order to view system status and operating information.
Additional features include:
• Temporary Idle
Slab protection for the snow melting system
• Boiler protection
• Manual Override
Adjustable Warm Weather Shut Down (WWSD)
Cold Weather Cut Out (CWCO)
Remote display and adjustment capabilities
Test sequence to ensure proper component operation
• Pump exercising
• Viscosity compensation
CSA C US Certifi ed (approved to applicable UL standards)
3
Red
4
Blk
5
Blu
6
Yel
7
Brn/
SlabMix Ret Sup
8
Boil
9
Com
10
tN2
11
Mix
12
Mix
13
Com
14
Out
15
Melt/Idle
Demand Pmp 2
16 17
System Boiler
18 21
Melting
22 23 25
Sys
P1
24
Power
L
N
Test
Snow Detector & Melting Control 667
Variable Speed Injection
Idle Demand
Signal wiring must be rated at least 300 V
Melt Demand
not testing
testing
testing paused
For maximum heat,
press and hold Test
button for 3 seconds.
Made in Canada by
tekmar Control Systems Ltd.
tektra 900-04
Power 115 V
± 10%
50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp
Var. Pump 230 V (ac) 2.4 A (FLA), 5A (LRA)
fuse T2.5 A 250V
Demand 20 to 260 V (ac) 2 VA
off
red
red
Do not apply power
19 20
Input
Outdoor
Sensor
Included
Input
Melt/Idle
Demand
Output
System
Pump
Output
System
Pump
Output
Variable Speed
Injection Pump
Input
115 V (ac)
Power
Supply
Input
Remote Display Module (RDM)
or
Remote Start / Stop Module
OR
Melt Demand
Idle Demand
WWSD
Minimum
Maximum
Water
Melting
Input
Snow/Ice Sensor
090 installed with
Sensor Socket
091 Optional
Input
Slab Sensor
Optional
or
Start
Menu Item
Stop
Do not apply power
Output
Melt Relay
Output
Boiler
1
Var
2
Pwr
H2029C
Input
Universal
Sensor
Included
Input
Universal
Sensor
Included
Input
Universal
Sensor
Included
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
Vue de la page 0
1 2 3 4 5 6 ... 31 32

Résumé du contenu

Page 1 - Date Code

1 of 32 © 2009 D 667 - 03/09- Data BrochureSnow Detector & Melting Control 667D 66703/09The Snow Detector & Melting Control 667 is a m

Page 2 - Menu Item

10 of 32© 2009 D 667 - 03/09External Melt Demand (DIP switch set to Melt Demand)The snow melting system is enabled when a voltage between 24 and

Page 3 - Definitions

11 of 3 2 © 2009 D 667 - 03/091516Melt / IdleDemand24 to 230 V (ac)LNIdle DemandMelt DemandExternal Idle Demand (DIP switch set to Idle Deman

Page 4 - Section A: General Operation

12 of 32© 2009 D 667 - 03/09Snow / Ice Sensor 090The slab temperature is displayed as SLAB in the VIEW menu. This temperature is calculated from

Page 5 - Section B: Snow Melting

13 of 32 © 2009 D 667 - 03/09Section G: Δ T Hours (Relative Energy Usage)Section G1 ΔT HoursSection G1: Δ T HoursThe control records the temp

Page 6 - 6 of 32

14 of 32© 2009 D 667 - 03/09InstallationCAUTIONImproper installation and operation of this control could result in damage to the equipment and p

Page 7 - Section C: Boiler Operation

15 of 32 © 2009 D 667 - 03/09Melt / Idle DemandTo generate a melt demand or idle demand, a voltage between 24 V (ac) and 240 V (ac) must be a

Page 8 - Differential

16 of 32© 2009 D 667 - 03/0913Com14Out Sensor and Unpowered Input ConnectionsDo not apply power to these terminals as this will damage the cont

Page 9 - Section D2

17 of 32 © 2009 D 667 - 03/09tekmar Net™ (tN2) DeviceA Remote Display Module (RDM) 040 or Remote Start / Stop Module 039 can be connected to

Page 10 - Melt Demand

18 of 32© 2009 D 667 - 03/09System Pump (System Pmp 2)If a pump is connected to the System Pmp 2 terminals (17 and 18), make sure power to the p

Page 11 - Section E: Melting Operation

19 of 32 © 2009 D 667 - 03/09LOCK / UNLOCK (FACTORY SETTING IS UNLOCK)The Lock / Unlock DIP switch is used to lock and unlock the access leve

Page 12 - Section F2

2 of 32© 2009 D 667 - 03/09Table of ContentsDIP Switch Settings ...Pg 18 Access Levels ...

Page 13 - Section G1

20 of 32© 2009 D 667 - 03/09 Outdoor Current outdoor air temperature as measured by the outdoor sensor. -67 to 149°F(-55 to 65°C)E1Slab Target S

Page 14 - –––––––––

21 of 32 © 2009 D 667 - 03/09Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINSTADV667 Adjust Menu (1 of 2)B1Run Time The t

Page 15 - © 2009 D 667 - 03/09

22 of 32© 2009 D 667 - 03/09C1Differential The differential for the snow melting system.Boil SENS = SUPAUTO, 2 to 42°F(AUTO, 1 to 23°C)Default

Page 16 - © 2009 D 667 - 03/09

23 of 32 © 2009 D 667 - 03/09667 Monitor Menu (2 of 3)Item Field DescriptionRangeAccessLevelLTDUSERINSTADVSlab Low The lowest recorded temper

Page 17 - 17 of 32

24 of 32© 2009 D 667 - 03/09667 Schd (Schedule) Menu (1 of 1)Item Field DescriptionRangeAccessLevelLTDUSERINSTADVOverride The setback override

Page 18

25 of 32 © 2009 D 667 - 03/09The Snow Detector & Melting Control 667 has a built-in test routine which is used to test the main control f

Page 19 - Access Levels

26 of 32© 2009 D 667 - 03/09When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following

Page 20 - 20 of 32

27 of 32 © 2009 D 667 - 03/09667 Error Messages (1 of 3)Error DisplayedDescription of ErrorThe control was unable to store a piece of informa

Page 21 - 21 of 32

28 of 32© 2009 D 667 - 03/09The control is no longer able to read the mixing supply sensor due to an open circuit. In this case, the control doe

Page 22 - 22 of 32

29 of 32 © 2009 D 667 - 03/09The control is no longer able to read the water detection circuit due to an open circuit. In this case, if the c

Page 23 - Item Field Description

3 of 32 © 2009 D 667 - 03/09DisplaySymbol DescriptionMixing Device Output ScaleShows output of injection pump. Arrows show whether the output

Page 24 - 24 of 32

30 of 32© 2009 D 667 - 03/09Notes

Page 25 - Menu Item or

31 of 32 © 2009 D 667 - 03/09Notes

Page 26 - Troubleshooting

Technical Data 32 of 32Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.Al

Page 27 - Description of Error

4 of 32© 2009 D 667 - 03/09Sequence of OperationSection AGeneralOperationPage 4 - 5Section BSnowMeltingPage 5 - 7Section CBoilerOperationPage 7 -

Page 28

5 of 32 © 2009 D 667 - 03/09Section B1: General Snow MeltingSLAB PROTECTION (ΔT MAX)The control can limit the rate at which heat is applied to

Page 29

6 of 32© 2009 D 667 - 03/09COLD WEATHER CUT OUT (CWCO)Maintaining the system at either the melting or idling temperature during extremely cold te

Page 30 - 30 of 32

7 of 32 © 2009 D 667 - 03/09Section C: Boiler OperationSection C1: Boiler Supply SensorSection C1Boiler SupplySensorSection C2Boiler ReturnSen

Page 31 - 31 of 32

8 of 32© 2009 D 667 - 03/09Section C3: No Boiler SensorNO BOILER SENSOR (Boil SENS = NONE)The 667 is capable of operating without a boiler sensor

Page 32 - Control Systems

9 of 32 © 2009 D 667 - 03/09Section D: Melting Enable / DisableSection D1Snow MeltingEnableSection D2Snow MeltingDisableSection D1: Snow Melti