One Stage Setpoint Control 150
12/08
D 150
HEAT
F
Setpoint
Differential
Delay/Cycle
The tekmar One Stage Setpoint Control 150 is a microprocessor-based control that
can be programmed
to maintain a fixed setpoint temperature by cycling a heating or cooling device using either bang-bang
or Pulse Width Modulated (PWM) output control.
This reliable and versatile control has a very wide setpoint range, an adjustable differential and time
delay that makes it useable in many different applications. The control has a digital LCD window that
normally shows the actual sensor temperature and can be used to view the setpoint as well as the other
programmed settings.
A Universal sensor 071 is supplied with the control. The wire to the sensor may be extended up to 500 ft.
(150m) by standard 18 AWG low voltage wire. The display will indicate a sensor fault whenever the
sensor is either open or short circuited.
Technical specifications
Settings
Temperature display — -85 to 302°F (-65 to 150°C)
Setpoint — -40 to 239°F (-40 to 115°C)
Differential (Bang/Bang) — 1 to 40°F (1 to 22°C)
Differential range (PWM) — 3 to 40°F (2 to 22°C)
Time delay (Bang/Bang) — 0 to 19 min. 50 sec.
(10 second increments)
Cycle length (PWM) — 30 sec. to 19 min. 50 sec.
(10 second increments)
Operating mode — Heating/Cooling
Temperature scale — Fahrenheit/Celsius
Programmed settings — Ten year memory
backup
• When the One Stage Setpoint Control 150 is powered-up
the digital display will show all of the display elements. The control
will then monitor the sensor temperature and display it in the digital display. (See diagram)
Technical Data
PRGM
HEAT COOL
FC
Hole for mounting screw
Wiring Chamber;
Terminals for
24Vac power
supply and
control circuit
for heating/
cooling device
Item
selection
and display
button
Wiring Chamber;
Terminals for
Sensor
°C or °F
indicators
Cooling mode
indicator
Programming
and display
buttons
Heating mode
indicator
Programming
mode indicator
Temperature,
Differential and
Delay/Cycle
Display
Bang - Bang Operating Mode
Bang-Bang control outputs turn equipment on when there is a demand for heating
or cooling, and then shut it completely off when the demand is satisfied.
• If the control is programmed for “Heat”
in this mode, it turns on its relay and
the “HEAT” display element when the sensor temperature is (a) — 1/2 the
differential setting below the setpoint,
and
(b) — the delay has timed out.
When the sensor
temperature rises 1/2 the differential setting above the
setpoint, the relay switches off , the “HEAT” display element turns off and the
delay starts to time out.
During the time out period, the Delay/Cycle pointer
will flash if heating is needed.
Sequence of Operation
Desired temperature
this example
160°F(71°C)
Temperature
WarmerCooler
Time
Differential
this example
1 0 °F ( 5 °C )
165°F(74°C)
155°F(68°C)
T
e
m
p
e
r
a
t
u
r
e
f
a
l
l
CONTROL RELAY (HEATING)
OFF ON
T
e
m
p
e
r
a
t
u
r
e
r
i
s
e
Item
Identifiers
Hole for mounting screw
PWM
Dip Switch Down
Dimensions 2-7/8" x 4-3/4" x 7/8”
)mm 22 x 021 x 47(
Gross Weight 1 lb (450g)
Ambient -20 to 120°F (-30 to 50°C)
gnisnednoc-non HR % 09<
Power supply 24 V (ac) ±10%, 50/60 Hz, 1.3 VA
A 20.0 %01± )cd( V 42
Relay 240 V (ac) 8 A 1/4 hp
Sensor 10 kΩ @77°F (25° ± 0.2°C),
rotsimreht CTN ,3 evruc
.tf 005 ot pu htiw etarucca
eriw eguag 81 fo )m051(
Control accuracy ±0.5°F (±0.3°C) at 70°F (21°C)
Item
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - - Data Brochure

- Data BrochureOne Stage Setpoint Control 15012/08D 150HEATFSetpointDifferentialDelay/CycleThe tekmar One Stage Setpoint Control 150 is a microprocess

Page 2 - Installation

CautionImproper installation and operation of this control could result in damage to equipment and possibly even personal injury.It is your responsibi

Page 3 - PROGRAM MODE

Push or tochange Delay/Cycle ItemItemPush or to select betweenFahrenheit or Celsius scalesThe control automatically goes back to opera

Page 4 - Testing and Troubleshooting

Differential (Bang - Bang)Setting the Differential on any control depends entirely on the actual operating characteristics of heating/cooling equipme